Fire triangle, causes & prevention

The fire triangle

Fire needs three things at once: heat (an ignition source), fuel (something that burns) and oxygen. Take away any one side of the triangle and the fire cannot start or cannot continue. Some texts call it the fire tetrahedron, adding a fourth element - the chemical chain reaction - but for fire marshal purposes the triangle is the model examiners expect.

Fire prevention strategy

Prevention works by controlling one or more sides of the triangle before ignition:

  • Control heat sources - safe use of electrical equipment, hot work permits, no smoking policies, keeping heaters clear of combustibles
  • Control fuel - good housekeeping, correct storage of flammable liquids and gases, clearing waste and packaging, minimising combustible loading
  • Control oxygen - keeping fire doors shut to limit air feeding a fire, using inert gas suppression in specialist areas, sealed storage for oxidising or flammable substances

Common causes of fire in the workplace

The usual culprits, again and again, are:

  • Electrical faults - overloaded sockets, damaged cables, unmaintained equipment
  • Arson - the single biggest cause of large workplace fires in the UK
  • Smoking materials - discarded cigarettes near combustible waste
  • Cooking equipment left unattended
  • Faulty or misused heaters
  • Poor housekeeping - accumulated rubbish, blocked ventilation, combustible storage too close to ignition sources

The role of the fire marshal

Under the Regulatory Reform (Fire Safety) Order 2005 (RRO 2005), the Responsible Person must carry out and keep under review a fire risk assessment covering ignition sources, fuel sources and the people at risk. Fire marshals support this by:

  • Spotting and reporting fire hazards as part of routine checks
  • Making sure escape routes and fire doors stay clear and unobstructed
  • Checking that flammable materials are stored correctly and away from ignition sources
  • Reinforcing good housekeeping standards day to day

Common mistakes candidates make

  • Confusing the fire triangle (heat, fuel, oxygen) with the extinguisher classes (which relate to fuel type, not the triangle)
  • Thinking removing oxygen means removing all air - in practice it means limiting the air supply reaching the fire, e.g. shutting a door
  • Forgetting that housekeeping (fuel control) is the most common and most preventable factor in workplace fires
  • Assuming arson only affects large sites - it is a leading cause across businesses of all sizes

Key numbers to remember

  • 3 sides to the fire triangle: heat, fuel, oxygen
  • 4 elements in the fire tetrahedron if a chain reaction is added
  • 1 element removed is enough to stop combustion
  • The fire triangle has exactly three elements: heat, fuel and oxygen - remove any one and the fire cannot burn
  • The fire tetrahedron adds a fourth element, the chemical chain reaction, but the triangle is the standard exam model
  • Arson is the leading cause of large fires in UK workplaces
  • Electrical faults - overloaded sockets and damaged cables - are a top recurring cause of workplace fires
  • Poor housekeeping (excess combustible waste and materials) is the most preventable fire risk factor
  • Controlling oxygen in practice means limiting air supply, such as keeping a fire door shut, not removing all air
  • The RRO 2005 places the duty for fire risk assessment on the Responsible Person, not the fire marshal alone
  • Fire marshals must ensure escape routes and fire doors remain unobstructed at all times
  • Hot work permits are a control measure aimed at the heat side of the fire triangle
  • Flammable liquids and gases must be stored correctly, away from ignition sources, to control the fuel side of the triangle
  • Fire risk assessments must be kept under review, not done once and filed away
  • Smoking materials and unattended cooking equipment remain classic real-world ignition sources
What are the three sides of the fire triangle?
Heat, fuel and oxygen
tap to reveal
What happens if you remove one side of the fire triangle?
The fire cannot start, or an existing fire cannot continue to burn
tap to reveal
What is the fire tetrahedron?
The fire triangle plus a fourth element, the chemical chain reaction
tap to reveal
What is the leading cause of large workplace fires in the UK?
Arson
tap to reveal
Give two examples of controlling the heat side of the fire triangle.
Hot work permits and safe use/maintenance of electrical equipment
tap to reveal
Give two examples of controlling the fuel side of the fire triangle.
Good housekeeping and correct storage of flammable liquids and gases
tap to reveal
How is the oxygen side of the fire triangle typically controlled in a building?
By limiting air supply to a fire, for example keeping fire doors shut
tap to reveal
What does poor housekeeping increase the risk of, and why?
Fire risk, because accumulated waste and combustible materials add fuel and can block ventilation or escape routes
tap to reveal
Under which law does the Responsible Person have to carry out a fire risk assessment?
The Regulatory Reform (Fire Safety) Order 2005 (RRO 2005)
tap to reveal
What must a fire risk assessment cover?
Ignition sources, fuel sources and the people at risk
tap to reveal
Name three common ignition sources found in workplaces.
Faulty electrics, discarded smoking materials, and unattended cooking or heating equipment
tap to reveal
What two things must fire marshals routinely check regarding escape routes?
That escape routes and fire doors are kept clear and unobstructed
tap to reveal
Why should flammable substances be stored away from ignition sources?
To break the link between the fuel and heat sides of the fire triangle and prevent ignition
tap to reveal
Is a fire risk assessment a one-off task?
No, it must be kept under review and updated as circumstances change
tap to reveal
Which is more common as a fire cause: electrical faults or lightning strikes?
Electrical faults, by a wide margin
tap to reveal

Fire safety law & the responsible person

Who is the 'responsible person'?

Under the Regulatory Reform (Fire Safety) Order 2005 (RRO), every non-domestic premises in England and Wales must have a 'responsible person'. This is usually the employer, but can also be the building owner, occupier, or anyone with control of the premises (eg a managing agent or landlord for common areas). If there is more than one responsible person in a shared building, they must cooperate and coordinate fire safety measures between them.

The core legal duty

The responsible person must carry out a suitable and sufficient fire risk assessment (FRA) and keep it under review. There is no fixed legal review interval, but it must be reviewed whenever there is reason to suspect it's no longer valid - eg after a fire, a near-miss, building works, a change of use, or a significant increase in staff or stock.

Written record threshold

If you employ 5 or more people, the significant findings of the FRA MUST be recorded in writing (this includes any group of 5+ across all premises, not just per-site). Below 5 employees it's not a strict legal requirement to write it down, but it is always best practice and strongly recommended - an unrecorded assessment is very hard to defend if things go wrong.

What 'suitable and sufficient' means

The FRA must identify: fire hazards (sources of ignition, fuel and oxygen), people at risk (including anyone especially vulnerable - the elderly, disabled, lone workers, visitors, sleeping occupants), and existing precautions, then evaluate and reduce the risk as far as reasonably practicable.

Enforcement and penalties

The local fire and rescue authority enforces the RRO. Inspectors can issue an Alterations Notice, Enforcement Notice, or Prohibition Notice (the latter stops use of premises immediately if there's a risk to life). Breaches are a criminal offence - unlimited fines and up to 2 years' imprisonment for serious breaches, and directors/managers can be personally prosecuted if the failure was due to their consent, connivance, or neglect.

Common exam mistakes

  • Confusing the RRO 2005 (England & Wales) with separate Scottish and Northern Irish fire safety legislation - don't assume UK-wide.
  • Thinking a fire risk assessment is a one-off tick-box exercise rather than a living document requiring review.
  • Assuming only the employer can be the responsible person - it can be anyone with control.
  • Believing under-5-employee premises never need anything written down - best practice still says do it.
  • The Regulatory Reform (Fire Safety) Order 2005 (RRO) governs fire safety law in England and Wales.
  • The responsible person is the employer, or anyone else with control of the premises (owner, occupier, managing agent).
  • A suitable and sufficient fire risk assessment (FRA) is a legal requirement for all non-domestic premises.
  • If 5 or more employees are employed, the significant findings of the FRA must be recorded in writing.
  • There is no fixed legal review period for an FRA - it must be reviewed when circumstances change or it's no longer valid.
  • Multiple responsible persons in one building have a legal duty to cooperate and coordinate.
  • Enforcement is carried out by the local fire and rescue authority.
  • A Prohibition Notice can immediately stop use of premises where there is a serious risk to life.
  • Breaching the RRO is a criminal offence carrying unlimited fines and up to 2 years' imprisonment.
  • Directors and managers can be personally prosecuted for breaches caused by their consent, connivance, or neglect.
  • The FRA must consider people especially at risk, such as disabled persons, lone workers, and sleeping occupants.
  • Scotland and Northern Ireland have separate fire safety legislation, not the RRO 2005.
What law governs fire safety in non-domestic premises in England and Wales?
The Regulatory Reform (Fire Safety) Order 2005 (RRO).
tap to reveal
Who counts as the 'responsible person' under the RRO?
The employer, or anyone else with control of the premises, eg owner, occupier, or managing agent.
tap to reveal
What must the responsible person carry out and keep updated?
A suitable and sufficient fire risk assessment (FRA), reviewed whenever it may no longer be valid.
tap to reveal
At what employee number does the FRA's findings have to be written down by law?
5 or more employees.
tap to reveal
Is there a fixed legal interval for reviewing a fire risk assessment?
No - it must be reviewed when circumstances change (eg after a fire, building works, increased occupancy).
tap to reveal
Who enforces the RRO 2005?
The local fire and rescue authority.
tap to reveal
What notice can immediately stop use of a building due to serious risk to life?
A Prohibition Notice.
tap to reveal
What are the maximum penalties for a serious breach of the RRO?
An unlimited fine and up to 2 years' imprisonment.
tap to reveal
Can a company director be personally prosecuted for a fire safety breach?
Yes, if the breach was due to their consent, connivance, or neglect.
tap to reveal
If a building has several responsible persons, what must they legally do?
Cooperate and coordinate their fire safety measures with each other.
tap to reveal
Name three groups the FRA must specifically consider as being at higher risk.
Disabled people, lone workers, and sleeping occupants (also elderly people and visitors).
tap to reveal
Does the RRO 2005 apply in Scotland?
No - Scotland and Northern Ireland have their own separate fire safety legislation.
tap to reveal
What three things must a fire risk assessment identify?
Fire hazards, people at risk, and existing precautions.
tap to reveal
What can inspectors issue if minor improvements are needed but the premises can still be used?
An Alterations Notice or Enforcement Notice (short of a full Prohibition Notice).
tap to reveal
Is an FRA a one-off task or an ongoing duty?
An ongoing duty - it's a living document that must be kept under review, not a one-off exercise.
tap to reveal

Detection, alarms & emergency lighting

Why detection and alarms matter

Under the RRO 2005 the Responsible Person must ensure a fire is detected quickly and everyone is warned in time to escape. The system chosen depends on the risk assessment - not every building needs the same level of protection.

Detection types

  • Automatic fire detection (AFD): smoke, heat or multi-sensor detectors linked to a central panel.
  • Manual call points (break-glass units): sited on escape routes, especially at exits and stairwell doors, so nobody has to travel more than about 45 metres to reach one on the way out.
  • Category naming (BS 5839-1) shows what a system protects: L1-L5 for life protection (L1 = most complete cover, detectors in nearly all areas) and P1-P2 for property protection.

Alarm sounders

  • A fire alarm must be audible throughout the building - the minimum standard is 65 decibels in all areas, or 5 decibels above any background noise if that is higher.
  • Where people sleep, sounders near the bed head must reach at least 75 decibels to wake someone.
  • Weekly test of the alarm system is standard practice, using a different call point or zone each week, at a pre-agreed time so it is not mistaken for a real fire.
  • A full test and service by a competent engineer should happen at least every six months.

Emergency lighting

  • Required wherever normal lighting failure would leave escape routes unlit, or in windowless rooms and large open areas.
  • Must provide at least 1 lux along the centre line of an escape route so people can see to walk out safely.
  • Standard duration is 3 hours of backup power, though 1 hour may be acceptable if the building is evacuated immediately and not re-occupied until power is restored.
  • Monthly function test (brief switch-over check) plus an annual full 3-hour duration test are both expected.
  • Emergency lighting should illuminate exit signs, changes of direction, stairs, fire equipment and final exit doors.

Common mistakes to avoid

  • Assuming a smoke alarm in a kitchen is fine - heat detectors are correct there to avoid false alarms from cooking.
  • Ignoring test records - a missed weekly or six-monthly test is a compliance failure even if the system works.
  • Ticking off emergency lighting on the plan but never actually testing the 3-hour duration.
  • Ignoring dB targets and installing sounders that cannot be heard over background noise.
  • Forgetting that call points still need to be within reach on every practical escape route, not just near the main entrance.
  • Fire alarm sounders must reach a minimum of 65 decibels throughout the building, or 5dB above background noise.
  • Sounders near sleeping areas (bed head) must reach at least 75 decibels to wake occupants.
  • Weekly alarm testing is standard, using a different call point/zone each week at an agreed time.
  • Full fire alarm system service should be carried out by a competent engineer at least every six months.
  • Emergency lighting must give a minimum of 1 lux along the centre line of an escape route.
  • Standard emergency lighting duration is 3 hours; 1 hour may be acceptable if the building is fully evacuated and not re-occupied until mains power returns.
  • Emergency lighting needs a monthly function test and a full annual 3-hour duration test.
  • BS 5839-1 category L1 gives the most complete life-protection detector coverage of a building.
  • Heat detectors, not smoke detectors, should be used in kitchens to prevent false alarms.
  • Manual call points should be positioned so no one has to travel more than about 45 metres to reach one.
  • Emergency lighting must cover exit signs, direction changes, stairways, fire equipment points and final exit doors.
  • The RRO 2005 requires detection and warning systems suitable to the findings of the fire risk assessment, not a one-size-fits-all standard.
What is the minimum sound level for a fire alarm throughout most of a building?
65 decibels (or 5dB above background noise if higher).
tap to reveal
What decibel level is needed for sounders near sleeping areas?
At least 75 decibels at the bed head, to wake a sleeping person.
tap to reveal
How often should the fire alarm be tested by staff?
Weekly, using a different call point or zone each time.
tap to reveal
How often should a competent engineer fully service the fire alarm system?
At least every six months.
tap to reveal
What is the minimum lux level required along an escape route under emergency lighting?
1 lux along the centre line of the escape route.
tap to reveal
What is the standard duration for emergency lighting backup power?
3 hours (1 hour may be acceptable only if the building is evacuated and stays empty until mains power is restored).
tap to reveal
How often must emergency lighting be tested?
Monthly brief function test, plus a full annual 3-hour duration test.
tap to reveal
What does BS 5839-1 category L1 mean?
The most comprehensive life-protection detector coverage, with detectors in nearly all areas of the building.
tap to reveal
Why should heat detectors be used instead of smoke detectors in kitchens?
To prevent false alarms caused by cooking smoke and steam.
tap to reveal
What is the guideline maximum travel distance to a manual call point?
About 45 metres.
tap to reveal
What must emergency lighting illuminate along an escape route?
Exit signs, changes of direction, stairways, fire-fighting equipment and final exit doors.
tap to reveal
What legal driver sets detection and alarm requirements in the UK?
The Regulatory Reform (Fire Safety) Order 2005, based on the findings of the fire risk assessment.
tap to reveal
What is a manual call point commonly known as?
A break-glass unit, sited on escape routes near exits and stairwell doors.
tap to reveal
What is the difference between L-category and P-category detection systems?
L-categories (L1-L5) protect life; P-categories (P1-P2) protect property.
tap to reveal

Evacuation, PEEPs & assembly

Why evacuation planning matters

A fire evacuation plan is only as good as its weakest link. The RRO 2005 places a legal duty on the 'responsible person' to prepare an emergency plan and make sure everyone in the building can get out safely, including staff, visitors and anyone with additional needs.

Assembly points

  • Every building needs at least one designated assembly point, sited a safe distance from the building (well clear of the fire exits, not blocking access routes for fire appliances).
  • If a building has multiple assembly points, each fire warden should know which one their zone uses.
  • A roll call must happen at the assembly point using an up-to-date register (staff list, visitor sign-in book, contractor log).
  • Nobody should re-enter the building for any reason, including pets or personal belongings, until the fire service confirms it is safe.
  • The assembly point should never be used as a car park muster area that blocks vehicle access.

PEEPs (Personal Emergency Evacuation Plans)

  • A PEEP is a bespoke plan for anyone who cannot self-evacuate unaided, for example wheelchair users, visually impaired people, or those with temporary injuries.
  • PEEPs must be agreed individually, in writing, and reviewed regularly, not assumed by a generic policy.
  • A GEEP (General Emergency Evacuation Plan) covers visitors or occasional users where an individual PEEP is not practical, using trained staff 'buddies' instead.
  • Evacuation lifts may only be used if specifically designed and certified for fire evacuation; ordinary passenger lifts must NEVER be used during a fire.
  • Refuge points (fire-protected areas, often on stairwell landings) allow a person to wait safely for assisted evacuation; they must have a means of two-way communication (an intercom or alarm point) to summon help.
  • PEEPs are not just for permanent staff; temporary and agency workers, and even short-term visitors with mobility needs, may need one arranged on the day.

Common mistakes to avoid

  • Assuming someone else has done the roll call.
  • Leaving assembly points too close to the building, or blocking the fire brigade access road.
  • Forgetting visitors and contractors are not on the usual staff register — sign-in sheets must be brought out too.
  • Confusing a refuge point with a place of ultimate safety — it is a temporary safe waiting area only, not the end of the evacuation.
  • Using a normal lift 'just this once' — heat and power loss can trap people inside.

Fire warden's role on the day

Sweep your designated zone (including toilets, stairwells and quiet rooms), close doors behind you to slow fire spread, direct people to the correct exit and assembly point, and report a clear headcount to the incident controller or fire service on arrival.

  • The RRO 2005 places the duty on the responsible person to prepare an emergency plan covering everyone in the premises.
  • Assembly points must be a safe distance from the building and must never block fire appliance access.
  • A roll call using an up-to-date register is mandatory at the assembly point.
  • Nobody re-enters the building for belongings or pets until the fire service confirms it is safe.
  • A PEEP is a written, individually agreed plan for anyone who cannot self-evacuate unaided.
  • A GEEP covers visitors or occasional users through trained staff buddies rather than an individual written plan.
  • Evacuation lifts can only be used if specifically certified for fire evacuation use.
  • Ordinary passenger lifts must never be used during a fire evacuation.
  • Refuge points must have two-way communication to summon assisted evacuation help.
  • A refuge point is a temporary safe waiting area, not a final place of safety.
  • Fire wardens must sweep their zone, including toilets and stairwells, and close doors behind them.
  • PEEPs must be reviewed regularly, not set once and forgotten.
What law requires an emergency evacuation plan covering everyone in the building?
The Regulatory Reform (Fire Safety) Order 2005, via the responsible person's duty.
tap to reveal
What must never block the route to an assembly point or be blocked by it?
Fire appliance (fire engine) access to the building.
tap to reveal
What must happen at the assembly point using a register?
A roll call, checking everyone is accounted for including visitors and contractors.
tap to reveal
When can people re-enter the building after evacuating?
Only once the fire service confirms it is safe — never for belongings or pets.
tap to reveal
What is a PEEP?
A Personal Emergency Evacuation Plan - a bespoke written plan for someone who cannot self-evacuate unaided.
tap to reveal
What is a GEEP?
A General Emergency Evacuation Plan for visitors or occasional users, using trained staff buddies instead of an individual PEEP.
tap to reveal
Can a normal passenger lift be used during a fire?
No, never - only a lift specifically certified as a fire evacuation lift may be used.
tap to reveal
What must a refuge point have to be valid?
A means of two-way communication, such as an intercom or call point, to summon assisted evacuation.
tap to reveal
Is a refuge point a final place of safety?
No, it is a temporary safe waiting area until assisted evacuation can happen.
tap to reveal
Who needs a PEEP arranged, besides permanent disabled staff?
Anyone who cannot self-evacuate unaided, including temporary staff, agency workers or visitors with mobility needs on the day.
tap to reveal
What should a fire warden do to their zone before leaving during a sweep?
Check toilets, stairwells and quiet rooms, then close doors behind them to slow fire spread.
tap to reveal
What should a fire warden report to the fire service on arrival?
A clear headcount from their zone via the incident controller.
tap to reveal
How often should a PEEP be reviewed?
Regularly - it must be kept up to date, not assumed to still apply indefinitely.
tap to reveal

Extinguisher types & safe use

Why extinguisher knowledge matters

A Fire Marshal is not expected to fight a fire, but you must know what is available, what it is for, and when NOT to use it. Tackling a fire is always optional and only for small, contained fires in their early stages - if in doubt, evacuate and let the fire brigade deal with it.

The colour-coding system

UK extinguishers are red-bodied with a coloured band showing the agent inside.

  • Water (red band) - Class A (wood, paper, textiles) only. Never use on electrical or burning fat/oil fires.
  • Foam (cream band) - Class A and Class B (flammable liquids). Safer than water on liquid spills.
  • CO2 (black band) - Class B and electrical fires. Leaves no residue, ideal for offices and server rooms.
  • Dry powder (blue band) - Multi-purpose, covers Class A, B and C (gases). Messy and reduces visibility, so avoid in confined spaces.
  • Wet chemical (yellow band) - Class F (cooking oils and fats) fires only. Designed for commercial kitchens.

Fire classes recap

  • Class A: solid combustibles (wood, paper, fabric).
  • Class B: flammable liquids (petrol, solvents, paint).
  • Class C: flammable gases (propane, butane).
  • Class D: metals (rare, needs specialist powder).
  • Class F: cooking oils and fats.
  • Electrical fires are not a lettered class but need a non-conductive agent (CO2 or powder).

Safe use - the PASS technique

  • Pull the safety pin.
  • Aim the nozzle at the base of the fire, not the flames.
  • Squeeze the handle gently.
  • Sweep side to side across the base of the fire.

Critical rules and common mistakes

  • Never use water or foam on live electrical equipment - risk of electrocution.
  • Never use water on a burning fat pan - it causes a violent fireball (steam explosion). Only wet chemical or a fire blanket is safe.
  • Always keep an exit behind you and never let the fire come between you and the door.
  • One extinguisher, one attempt - if it does not work in seconds, leave and raise the alarm.
  • CO2 extinguishers get very cold when discharged - hold only by the horn's insulated handle, never the horn itself, to avoid cold burns.
  • Extinguishers must be serviced annually (BS 5306-3) and wall-mounted with the top handle roughly 1 metre from the floor.
  • Powder extinguishers are unsuitable for use in small enclosed spaces due to inhalation risk and loss of visibility.
  • Water extinguishers (red band) are for Class A materials only - never on electricals or fat fires.
  • Foam extinguishers (cream band) cover Class A and Class B flammable liquids.
  • CO2 extinguishers (black band) are correct for electrical fires and Class B liquids, and leave no residue.
  • Dry powder extinguishers (blue band) cover Class A, B and C but are unsuitable for confined spaces.
  • Wet chemical extinguishers (yellow band) are for Class F cooking oil and fat fires only.
  • Never use water or foam on a live electrical fire - electrocution risk.
  • Never use water on a burning fat pan - it causes a steam explosion fireball.
  • PASS technique: Pull, Aim at the base, Squeeze, Sweep side to side.
  • Extinguishers must be serviced annually to BS 5306-3.
  • CO2 horns get extremely cold in use - hold the insulated handle, never the horn.
  • Class D fires (burning metals) need a specialist powder extinguisher, not standard types.
  • Only tackle a fire if it is small, contained, in its early stages, and you have a clear escape route.
What colour band identifies a water extinguisher?
Red band - for Class A materials only.
tap to reveal
What colour band identifies a CO2 extinguisher?
Black band - used on electrical fires and Class B liquids.
tap to reveal
What colour band identifies a foam extinguisher?
Cream band - covers Class A and Class B fires.
tap to reveal
What colour band identifies a dry powder extinguisher?
Blue band - multi-purpose for Class A, B and C.
tap to reveal
What colour band identifies a wet chemical extinguisher?
Yellow band - for Class F cooking oil and fat fires only.
tap to reveal
Why must you never use water on a chip pan fire?
It turns instantly to steam and causes a violent fireball (steam explosion).
tap to reveal
What does PASS stand for?
Pull the pin, Aim at the base, Squeeze the handle, Sweep side to side.
tap to reveal
Which extinguisher type is safe for live electrical equipment?
CO2 - it is non-conductive and leaves no residue.
tap to reveal
Why should you never grip the horn of a CO2 extinguisher?
It becomes extremely cold during discharge and can cause cold burns - hold the insulated handle instead.
tap to reveal
What is Class F fire?
Cooking oils and fats, typically in commercial kitchens.
tap to reveal
What is Class C fire?
Flammable gases such as propane or butane.
tap to reveal
How often must extinguishers be professionally serviced?
Annually, to BS 5306-3.
tap to reveal
Why avoid dry powder extinguishers in small enclosed rooms?
They reduce visibility and pose an inhalation risk in confined spaces.
tap to reveal
What is the golden rule before attempting to fight any fire?
Only tackle it if small and in its early stages, and always keep a clear escape route behind you.
tap to reveal
At what point should you stop trying to extinguish a fire yourself?
If it is not out within seconds of your attempt - leave immediately and raise the alarm.
tap to reveal

Fire risk assessment basics & housekeeping

What a fire risk assessment actually is

Under the Regulatory Reform (Fire Safety) Order 2005 (RRO), the 'responsible person' for a building must carry out a suitable and sufficient fire risk assessment (FRA) and review it regularly. As a marshal or warden you won't usually write the FRA, but you must understand it, know where it's kept, and feed hazards back into it.

The five steps

  • Identify fire hazards: ignition sources (naked flames, hot processes, electrical faults), fuel (paper, packaging, furniture, chemicals), and oxygen sources.
  • Identify people at risk: staff, visitors, contractors, and especially those especially at risk - lone workers, people with disabilities, members of the public unfamiliar with the layout.
  • Evaluate, remove or reduce the risks: get rid of the hazard where possible, or control it (safe storage, hot work permits, ignition control).
  • Record findings, prepare an emergency plan, and provide training - a written record is a legal must if you employ 5 or more people.
  • Review regularly and after any significant change - new layout, new equipment, a near miss, or a change in staff numbers.

Housekeeping - the daily discipline

Good housekeeping is the cheapest and most effective fire prevention tool there is.

  • Keep combustible waste (paper, cardboard, packaging) to a minimum and remove it at the end of each day.
  • Never prop open fire doors - they hold back smoke and fire for a set time (commonly 30 or 60 minutes, shown as FD30/FD60) and only work if kept shut.
  • Keep escape routes and fire exits completely clear - no storage, no furniture, not even 'just for five minutes'.
  • Keep final exits unlocked and available whenever the building is occupied.
  • Don't overload sockets or leave portable heaters unattended near combustibles.
  • Store flammable liquids and chemicals in a proper, ventilated, fire-rated cabinet or store, away from ignition sources.
  • Check that fire extinguishers, alarm call points and signage are unobstructed and visible.

Common mistakes to spot on patrol

  • Fire doors wedged open with a chair or fire extinguisher.
  • Boxes or bikes stacked in a corridor that's also an escape route.
  • Extension leads daisy-chained together or overloaded.
  • Smoking materials disposed of in a normal bin rather than a metal one.
  • Fire risk assessment out of date - it should be a living document, reviewed at least annually or after any change.

As a marshal, your job is to notice these day to day, correct what you safely can, and escalate the rest to the responsible person straight away.

  • The RRO 2005 requires a 'responsible person' to carry out a suitable and sufficient fire risk assessment.
  • The FRA must be recorded in writing if the organisation employs 5 or more people.
  • The five steps of an FRA are: identify hazards, identify people at risk, evaluate/remove/reduce risk, record and plan, review regularly.
  • Fire doors are rated by how long they hold back fire - FD30 means 30 minutes, FD60 means 60 minutes.
  • Fire doors must never be wedged or propped open unless fitted with an approved automatic release device.
  • Escape routes and final exits must be kept completely clear and unlocked whenever the premises are occupied.
  • Combustible waste such as paper and cardboard should be removed regularly, not left to accumulate.
  • Flammable liquids must be stored in a fire-rated, ventilated cabinet away from ignition sources.
  • The FRA must be reviewed regularly and immediately after any significant change to the building, process or occupancy.
  • Smoking materials should be disposed of in a metal bin, never a standard waste bin.
  • Overloaded sockets and daisy-chained extension leads are a common electrical ignition hazard flagged on patrol.
  • Marshals should escalate any FRA gap or hazard they cannot fix themselves to the responsible person immediately.
What law requires a fire risk assessment in the UK?
The Regulatory Reform (Fire Safety) Order 2005 (RRO).
tap to reveal
Who is legally required to carry out the fire risk assessment?
The 'responsible person' for the premises.
tap to reveal
At what staff headcount does the FRA legally have to be written down?
5 or more employees.
tap to reveal
Name the five steps of a fire risk assessment.
Identify hazards; identify people at risk; evaluate/remove/reduce risk; record findings and plan; review regularly.
tap to reveal
What does FD30 mean on a fire door?
The door will hold back fire for 30 minutes.
tap to reveal
Can a fire door ever be legitimately held open?
Only if fitted with an approved automatic release device linked to the fire alarm - never with a wedge or chair.
tap to reveal
How should flammable liquids be stored?
In a fire-rated, ventilated cabinet or store, away from any ignition source.
tap to reveal
How should smoking materials be disposed of?
In a metal bin, never a standard combustible waste bin.
tap to reveal
When must an FRA be reviewed, aside from routine intervals?
Immediately after any significant change - new layout, new equipment, a near miss, or altered staff numbers.
tap to reveal
What is the single cheapest, most effective fire prevention measure?
Good housekeeping - keeping combustible waste down and escape routes clear.
tap to reveal
What should never block an escape route, even briefly?
Storage, furniture, or any obstruction - escape routes must always stay fully clear.
tap to reveal
What are the three components of the fire triangle that hazard identification targets?
Ignition source, fuel, and oxygen.
tap to reveal
What is a common electrical housekeeping hazard to spot on patrol?
Overloaded sockets or daisy-chained extension leads.
tap to reveal
Who should a marshal tell if they spot an FRA gap they can't fix themselves?
The responsible person, escalated immediately.
tap to reveal
Must final exits be locked or unlocked while a building is occupied?
Unlocked and immediately available at all times the building is occupied.
tap to reveal