BS 7671 is split into Parts. Part 1 sets the scope - what the regulations apply to. Part 2 gives the definitions used throughout the rest of the book. Get these wrong in the exam and you will misread every later question, because terms like 'circuit', 'skilled person' and 'exposed-conductive-part' all have precise legal meanings, not everyday ones.
Part 4 of BS 7671 covers three separate hazards: electric shock, thermal effects (fire and burns), and overcurrent (overload and fault current). Each has its own chapter and its own set of rules, but they interact — a device sized to clear a fault fast enough also limits the energy that could start a fire.
Basic protection stops contact with live parts (insulation, barriers, enclosures to at least IP2X or IPXXB, or IP4X/IPXXD on horizontal top surfaces). Fault protection stops a fault from becoming dangerous, mainly via automatic disconnection of supply (ADS).
Protection against fire is about keeping fault energy and surface temperatures away from combustible material and skin. Devices, enclosures and cables must be selected so normal operation doesn't create excessive heat, and arc fault detection devices (AFDDs) are increasingly recommended (and sometimes required) in higher-risk locations like HMOs and buildings with sleeping accommodation.
Overcurrent is split into overload (too much current in a healthy circuit) and fault current (short circuit or earth fault). The classic design rule is the three-part inequality: Ib is less than or equal to In is less than or equal to Iz, and I2 is less than or equal to 1.45 times Iz.
Learn the disconnection-time table (41.1) cold — TN vs TT, final vs distribution circuit. Know which situations mandate 30mA RCDs regardless of calculation. And always check both halves of the overload equation, not just the first.
Part 5 of BS 7671 covers how you choose and install equipment so it survives its environment and doesn't become a hazard. Every piece of kit must suit the voltage, current, frequency, power, and the external influences it will face (damp, dust, impact, corrosion, vibration).
Revise the IP code table, the wall cable zones, and the isolation rules first - these come up again and again in exam questions on Part 5.
Part 6 of BS 7671 covers initial verification (new work) and periodic inspection (existing installations). Every installation must be inspected and tested before being put into service, and a certificate issued confirming it meets the requirements of BS 7671 as amended.
Always inspect before testing, and with the installation dead where practicable. Inspection checks things testing cannot, such as correct cable selection, connections, and protection against fire spread, before any power is applied.
1. Continuity of protective conductors (including main and supplementary bonding).
2. Continuity of ring final circuit conductors.
3. Insulation resistance.
4. Polarity.
5. Earth electrode resistance (where applicable, eg TT systems).
Once dead tests pass, live tests follow: earth fault loop impedance (Zs), prospective fault current, and RCD operation (using an RCD tester, checking trip times at rated and 5x rated current). Functional testing of switchgear, RCDs (test button) and interlocks completes the process.
EICR recommended intervals: domestic 10 years (or change of occupancy), commercial 5 years, rented domestic property 5 years (or change of tenancy), swimming pools/agricultural 1-3 years, construction sites 3 months. Observations are coded C1 (danger present, immediate action), C2 (potentially dangerous, urgent remediation), C3 (improvement recommended), or FI (further investigation required).
Ordinary rules assume dry, low-risk surroundings. Part 7 of BS 7671 bolts on extra protection for locations where water, confined space, high body-current risk, or unusual hazards make a standard installation unsafe. Each section (601 to 753 and beyond) covers one location type with its own zone diagram and rules.
BS 7671 Appendices turn the regulations into usable design data. For the exam you need to know which appendix holds what, and be able to apply the tables under time pressure.
This is the big one. It gives current-carrying capacity (Iz) tables for different installation methods, reference methods (like Method C clipped direct, Method 100/101 for cables in insulation), and correction factors:
The design current Ib must be less than or equal to In (the protective device rating), which must be less than or equal to Iz (the tabulated rating times all correction factors). This is Regulation 433.1.1, often written Ib <= In <= Iz.
After sizing for current, you must always check voltage drop (Appendix 4 tables give mV/A/m values) against the limits in Appendix 12: 3% for lighting, 5% for other uses, from the origin of the installation.
Works with Appendix 4 for disconnection time verification, especially useful for checking maximum earth fault loop impedance against device type and rating.
Appendix 1 (previously often referenced as the diversity guidance, formerly IEE On-Site Guide material) allows you to apply diversity factors when calculating the total assumed current demand of an installation - you rarely add up every circuit at 100% because not everything runs at once. Typical examples: 100% of largest cooker circuit plus 30% of the rest, or 66% for socket outlet circuits in some premises. Diversity is about assessing realistic maximum demand, not a safety margin you can invent - always use the recognised published percentages.
Appendix 7 gives the standard graphical and letter symbols used on electrical drawings and schedules (switches, sockets, distribution boards, cable types). Exam questions often show a symbol and ask you to identify it, or ask which appendix a symbol comes from.